RCD protection explained: what it does and how to test it

What an RCD does, how it differs from a circuit breaker and an RCBO, how to test it, why it trips, and why many older NZ homes do not have one.

By Plexus ElectricalPublished 6 min read

An RCD (residual current device) is a safety switch that turns the power off very quickly when it detects electricity leaking to earth, for example through a person who has touched something live. A circuit breaker does a different job: it protects the wiring from overload and short circuits, but it will not protect you from a shock. An RCBO combines both in one device. New lighting and power circuits in New Zealand must be RCD protected, but many older homes have no RCDs at all. You can test an RCD yourself with its test button. Anything beyond that is work for a licensed electrician.

What an RCD does

Electricity normally flows out along the active conductor and back along the neutral. An RCD constantly compares the two. If some of the current is not coming back, it is leaking somewhere else, often to earth, and possibly through someone. The RCD detects that imbalance and switches the circuit off.

WorkSafe's code of practice for homeowners (NZECP 51) says an RCD used for personal protection "will protect you from receiving a fatal electric shock, if a fault to earth occurs in an electrical installation", and that it must be rated at 30 mA. Those devices are common in New Zealand homes in three forms:

  • On the switchboard, protecting lighting and socket circuits. These have an operating switch and a "test" button.
  • Built into a socket-outlet, often in a bathroom, laundry or garage. These have "test" and "reset" buttons on the faceplate.
  • Portable RCDs that plug into a socket, used with outdoor tools such as hedge trimmers and lawnmowers.

An RCD has limits. NZECP 51 points out that an RCD will not protect you if you touch the active and neutral at the same time, and it does not replace safe work practice. It also does not protect against overload, which is why a circuit still needs a circuit breaker or fuse.

RCD vs circuit breaker vs RCBO

Device What it protects against How to recognise it
Circuit breaker (MCB) Overload and short circuit on the wiring A toggle switch, no test button
RCD Current leaking to earth, including through a person A switch plus a "T" or "Test" button
RCBO Both, for a single circuit A single device with a toggle and a test button
Rewireable fuse Overload only Ceramic or plastic carriers with fuse wire inside

NZECP 51 warns that RCDs "are not to be confused with circuit-breakers, which are similar in appearance; circuit-breakers will not protect you from receiving an electric shock."

RCD shared across circuits, or one RCBO per circuit?

A common arrangement is one RCD protecting a group of circuits. It works, but if one appliance or circuit develops a fault, every circuit on that RCD goes off, which might mean the fridge, the lights and the home office at once. An RCBO protects just one circuit, so a fault only affects that circuit. Boards built with RCBOs usually cost more, but are easier to live with and make faults quicker to find. Your electrician can explain which approach suits your board and budget.

Special types

Some equipment needs a particular type of RCD. EECA, for example, advises a Type B RCD for an EV wall charger, and WorkSafe's EV charging guidelines say RCDs for charging equipment should keep protecting, or disconnect the supply, when there is more than 6 mA of DC fault current. That is a more demanding job than the RCDs protecting ordinary socket circuits are built for. If you are adding a charger, your electrician should specify the RCD type the charger needs.

Why older homes often lack RCDs

NZECP 51 explains that from 1 January 2003, the Electricity Regulations required new domestic installations to have RCDs on the main switchboard protecting all lighting and socket-outlet circuits, and that new circuits added to an existing installation also need RCD protection. Before that, a house might have had a single socket-type RCD in the bathroom or laundry, or none at all.

Level (BRANZ) states the current position: "all new lighting and power outlet circuits installed in electrical installations must be protected by one or more RCDs", which does not apply to permanently connected appliances.

So a house built before 2003, or one with an original fuse board, may have little or no shock protection. That is one of the most common reasons we recommend a switchboard upgrade.

How to test an RCD

Testing is one of the few electrical checks a homeowner should do. NZECP 51 recommends:

  • Switchboard RCDs: test at the start and end of daylight saving by pressing the "test" button.
  • Socket-outlet RCDs: test monthly. Run an appliance from the socket, press the test button, and the appliance should turn off.
  • Portable RCDs: test each time you use one. Plug it directly into the wall socket, test it, reset it, then plug in your tool or lead.

Step by step for a switchboard RCD:

  1. Warn the household, and save any work on computers. The test switches off power to everything on that RCD.
  2. Press the test button firmly. The RCD's switch should flick to the off or mid position and the power on those circuits should go off.
  3. Reset it by pushing the switch back to "ON" or "I" until it clicks.
  4. Reset clocks and timers on appliances such as ovens and heat pumps if needed.

NZECP 51 is clear about failures: "Never use an RCD if the 'test' button fails to turn off". Seek advice from a licensed electrical worker, because the RCD may need replacing. Do not open the switchboard to investigate.

Why RCDs trip, and what to do

An RCD that trips is usually doing its job. Common causes include:

  • A faulty appliance, such as a kettle, heater or washing machine with a damaged element or moisture inside.
  • Damaged leads or tools, especially outdoors.
  • Moisture in an outdoor light, socket or junction box after rain.
  • Many appliances on one RCD. NZECP 51 notes that some appliances, such as computers, have a small normal leakage current, and an appliance can test clear on its own but trip the RCD when combined with another.
  • A wiring fault in the fixed wiring.

NZECP 51's suggested approach when an RCD keeps tripping:

  1. Unplug all appliances on the affected circuits.
  2. Reset the RCD.
  3. Plug appliances back in and turn them on one at a time.
  4. If one appliance trips the RCD, stop using it until it has been repaired.

Call an electrician if the RCD trips with nothing plugged in, will not reset, trips in wet weather, or trips only when several appliances are used together. Those point to a wiring fault, a moisture problem or a board that needs reorganising. Plexus offers fault finding across Auckland.

When an electrician adds RCD protection

RCDs on the switchboard must be installed by a licensed electrician. This is not homeowner work; our guide to what electrical work you can do yourself sets out the limits. Common situations where an electrician adds RCDs:

  • A switchboard upgrade, where every lighting and socket circuit is brought under RCD or RCBO protection.
  • New circuits, for a renovation, extension, heat pump or EV charger. New lighting and power circuits must be protected.
  • Outdoor power and lighting, where wet conditions increase the risk. See our outdoor lighting guide.
  • After an inspection of an older home that finds no RCD protection.

Before adding RCDs to an older house, the electrician should test the existing wiring. Old or damaged insulation can cause an RCD to trip constantly, and that is better found before the work is quoted.

Next steps

Press the test button on your board this week. If you cannot find an RCD, the test fails, or it trips more than it should, have it looked at. Plexus can test your circuits and quote a switchboard upgrade that brings every circuit under modern protection. Request a quote and include a photo of your switchboard with the cover closed.

Sources

  1. WorkSafe: NZECP 51:2004 Code of practice for homeowner/occupier's electrical wiring work in domestic installations
  2. Level (BRANZ): Internal electrical power services
  3. WorkSafe: Cords and leads
  4. EECA: Charging your EV at home and on the road
  5. WorkSafe Energy Safety: Electric vehicle charging safety guidelines, 2nd edition (May 2019)
  6. Electricity (Safety) Regulations 2010

This guide is general information for New Zealand homes, not advice for your specific property. For a recommendation that accounts for your house, ask us.

FAQ

Frequently asked questions

What is the difference between an RCD and a circuit breaker?

A circuit breaker protects the wiring from overload and short circuits. An RCD protects people: it switches off very quickly when it detects current leaking to earth, which is what happens when someone gets a shock. WorkSafe's homeowner code of practice is clear that circuit breakers will not protect you from an electric shock.

How often should I test my RCD?

WorkSafe's code of practice for homeowners (NZECP 51) suggests testing switchboard RCDs at the start and end of daylight saving, testing socket-outlet RCDs monthly, and testing a portable RCD each time you use it. Always follow the instructions on the device.

What should I do if my RCD keeps tripping?

Unplug everything on the affected circuits, reset the RCD, then plug appliances back in one at a time. If one appliance trips it, stop using that appliance until it is repaired. If the RCD trips with nothing plugged in, or will not reset, leave it off and call an electrician.

Is an RCBO better than an RCD?

An RCBO combines a circuit breaker and an RCD in one device for a single circuit, so a fault on one circuit only switches that circuit off. A shared RCD protects several circuits at once, so one fault can turn them all off. Both give shock protection. Which suits your board is a design decision for your electrician.

Does my house need RCDs?

New lighting and power circuits must be RCD protected. Older homes built before the requirement often have none, or only one on a bathroom or laundry socket. If you cannot see a device with a test button on your board, ask an electrician to check what protection you have.